PHOENIX CONTACT FEED THROUGH TERMINAL BLOCK - TB 4 EI

PHOENIX CONTACT FEED THROUGH TERMINAL BLOCK - TB 4 EI

 

Number of levels: 1

Nominal cross section : 4 mm²

Number of connections: 2

Rated surge voltage: 8 kV

Pollution degree: 3

Connection in acc. with standard: IEC 60947-7-1

Shock protection test specification: DIN EN 50274 (VDE 0660-514):2002-11

Bending test rotation speed: 10 rpm

Conductor cross section tensile test: 0.5 mm²

Conductor cross section tensile test: 6 mm²

Conductor cross section tensile test: 4 mm²

Requirements, voltage drop:  ≤ 3.2 mV

Conductor cross section short circuit testing: 4 mm²

Short-time current: 0.48 kA

 

Maximum load current: 32 A

Nominal current IN: 32 A

Nominal voltage UN: 800 V (in the case of enclused clamping space) 

Surge voltage test setpoint: 9.8 kV

Power frequency withstand voltage setpoint: 2 kV

Proof of thermal characteristics (needle flame) effective duration: 30 s

Temperature index, insulating material (DIN EN 60216-1 (VDE 0304-21)): 125 °C

Note: Terminal point

Connection method: Screw connection

Connection in acc. with standard: IEC 60947-7-1

Conductor cross section AWG min: 20

Conductor cross section AWG max: 10

Min. AWG conductor cross section, flexible: 20

Max. AWG conductor cross section, flexible: 12

Stripping length: 8 mm

Screw thread: M3

Tightening torque, min: 0.5 Nm

Tightening torque max: 0.6 Nm

 

Width: 6.2 mm

End cover width: 1.8 mm

Length: 42.5 mm

Height NS 35/7,5: 47 mm

Height NS 35/15: 54.5 mm

Height NS 32: 52 mm

PHOENIX CONTACT FEED THROUGH TERMINAL BLOCK - TB 4 EI

SKU: TB-4-EI
  • 4 to 6 weeks on request.!